Performance improvement of resonant multi-loop controller with odd harmonic injection for standalone three-phase inverter

نویسندگانMohsen Karimi , Mohammad Pichan , Seyed Morteza Seyedjafari
نشریهWorld Journal of Engineering
نوع مقالهFull Paper
تاریخ انتشار2019-6-Nov
رتبه نشریهISI
نوع نشریهچاپی
کشور محل چاپایران

چکیده مقاله

 This paper aims to investigate an improved control method and digital signal processor-based (DSP-based) digital implementation of three-phase standalone inverter. The proposed method is performance developed of the proportional-resonant controller (PRC) with harmonic injection technique, aiming to improve load voltages quality under different loads, especially nonlinear loads. The advanced proposed multi-loop controller is consisted of current harmonic loops for suppressing odd harmonic, which are analyzed in discrete-time domain. Besides, the voltage loop is also used to compensate the output capacitor voltage.
Design/methodology/approach – The proposed method can effectively enlarge output voltage stability with low total harmonics distortion and improve the dynamic transient response. The other advantage of the proposed PRC is the injection of the selective harmonic without any additional calculation compensator.
Findings – The method is given the opportunity to be controlled exactly all harmful outputs with high-quality voltage referenced of the standalone inverter. The proposed method is implemented using a DSP processor (TMS320F28335) and is verified on the 10 kVA three-phase standalone inverter prototype.
Originality/value – The proposed method is performance developed of the PRC with harmonic injection technique, aiming to improve load voltages quality under different loads, especially nonlinear loads.